0 Starting test '.\H2_PERM.SCE' at Thu Jun 19
1402 # …
1402 # … Get All Systems Running
1422 Subtest 'STARTALL.SCE' started--nest level 1
1452 Subtest 'H4_START.SCE' started--nest level 2
1462 Subtest 'H4_PURGE.SCE' started--nest level 3
1402 # …
1402 # … Turn i17HS0669B OFF, Field Trip for Heater
8813 # … Get Heater Ready to Purge
8813 # … Set Level i17LT1641 to 10
10215 # … Turn all bypass switches ON, OFF is bypass
11617 # … Turn i17FSLL1998, i17XSC3726, and i17XSC3721 ON to Satisfy Limit
17225 # Test at line 12 of 'PURGE.SCT' ON i17FSLL1998,...
17225 Verification <i17YL1973> = 1.000000 passed
17225 # … Lo CO In Heater, Start Purge
23033 # Test at line 14 of 'PURGE.SCT' ON i17HS1974
23033 Verification <i17YL1973> = 0.000000 passed
23033 Verification <i17YL1975> = 1.000000 passed
23033 # … Pause Scenario Until Purge is Done, i17YL1976
50172 # … Verify Purge Is Completed
50172 # Test at line 20 of 'PURGE.SCT' ASSERT
50172 Verification <i17YL1975> = 0.000000 passed
50172 Verification <i17YL1976> = 1.000000 passed
50172 # …
50242 Subtest 'H4_PILOT.SCE' started--nest level 3
50172 # …
50172 # … Turn all bypass switches ON, OFF is bypass
55980 # … Reset i17HS0669RST and i17HS1982RST, ESD and Fuel Gas Trips
67196 # … Start Pilot
72805 # Test at line 9 of 'PILOT.SCT' ON i17HS1977
72805 Verification <i17XY1971> = 1.000000 passed
72805 Verification <i17YL1976> = 0.000000 passed
72805 Verification <i17YL1999> = 1.000000 passed
72805 # … Pilot PB Verification
78613 # Test at line 11 of 'PILOT.SCT' ON i17HS1979
78613 Verification <i17YL1999> = 0.000000 passed
78613 Verification <i17YL1980> = 1.000000 passed
78613 # …
78663 Subtest 'H4_BRNR.SCE' started--nest level 3
78613 # …
78613 # … Reset i17HS1982RST, Fuel Gas Trip
90029 # … Start Main Burner
95838 # Test at line 7 of 'BRNR.SCT' ON i17HS1981
95838 Verification <i17XY0533A> = 1.000000 passed
95838 Verification <i17XY0533B> = 1.000000 passed
95838 # … Verify Main Burner Ignition
100444 # Test at line 9 of 'BRNR.SCT' ON i17HS2408
100444 Verification <i17YL1980> = 0.000000 passed
100444 # … Reset BFW Flow/Steam Drum Level Trip
115366 # … Reset Level Switch i17HS2406A
126582 # …
130788 # … Verify All Systems Are Running
# …
# Heater Permissives Test Complete
Closing
test log after 2 mins 26.7 secs at Thu Jun 19